Technical Tests

1- Internal Use Standard IM Panels

Dimensions of the panel : 4000 x 1200 mm
Thickness of the panel : 20 mm
Thickness of the external aluminum foil : 60 microns embossed
Thickness of the internal aluminum foil : 60 microns embossed
Density of the foam : 45 kg/m3
Weight of the panel : 1,40 kg/m²
Aluminum finishing : embossed / embossed
The external aluminum foil is lacquered with a weatherproof and ultraviolet rays protecting epoxy varnish.

Insulating Characteristics

Insulating material : Close cell rigid expanded pir foam, without CFC and HCFC. Material physiologically and chemically inert, insoluble.
Thermal Conductivity: 0,0216 W/mK
Foam density: 45 Kg/m3
The aluminum foils covering the panel assure a perfect vapor barrier.

Pressure Of Use

The air ducts fabricated with IM PIR 60/60 panels can be used in installations with pressures up to 1750 Pa, always in accordance with the construction standards fixed by IM.

Temperature Of Use

The air ducts fabricated with IM 60/60 panels can be used in installations with temperatures ranging from -35°C to +110°C, always operating. No relevant reduction of the insulating, chemical or physical characteristics of the panel will be observed.

Handling Warning

During all handling processes, wear gloves

Specification Of Use

The air ducts fabricated by using IM panels can be installed in plants: - with air speed up to 35 m/s - with pressures up to 1750 Pa
- indoor and/or outdoor
IM 60/60 panels are particularly fit for the construction of air ducts to be installed in:
- Hospitals
- Surgical Rooms
- Clean Rooms
- Pharmaceutical Industries
- Food industries

2- External Use

IM PIR PANEL 200/80
Technical Characteristics
Dimensions of the panel : 4000 x 1200 mm
Thickness of the panel : 30 mm
Thickness of the external aluminum foil : 200 microns embossed
Thickness of the internal aluminum foil : 80 microns
Density of the foam : 48 kg/m3
Weight of the panel : 2,20 kg/m²
aluminum finishing : imposed / imposed
The external aluminum foil is lacquered with weatherproof and ultraviolet rays protecting epoxy varnish.

Insulating Characteristics

Insulating material: Close cell rigid expanded pir foam, without CFC and HCFC
Thermal Conductivity: 0,0220 W/mK
Foam density: 48 Kg/m3

Temperature Of Use

The air ducts fabricated with IM panels can be used in installations with temperatures ranging from -35°C to +110°C, always operating. No relevant reduction of the insulating, chemical or physical characteristics of the panel will be observed.

Pressure Of Use

The air ducts fabricated with our panels can be used in installations with pressures up to 1750 Pa, always in accordance with the standard construction.

Handling Warning

During all handling processes, wear gloves.

Specification Of Use

The air ducts fabricated by using IM panels can be installed in plants:
- with air speed up to 35 m/s
- with pressures up to 1750 Pa
- indoor or outdoor
IM panels are particularly fit for the construction of air ducts to be installed in:
- Hospitals
- Surgical Rooms
- Clean Rooms
- Pharmaceutical Industries
- Food industries
The particular strength of the panel makes it particularly fit for the fabrication of ducts with large sections.

TECHNICAL TESTS
Characteristic   Standard    Result
Panel Stiffness / Rigidity EN 13403  353.000 N•mm
Resistance to high pressure EN 13403 
Resistance to positive/negative pressure IM     +3800 Pa / -4200 Pa No breakages or loss of functionality
Air leakage (Positive/Negative Pressure) EN 1507     Class “C” and “B”  
Air pressure drop inside ductwork           Negligible
Resistance to high temperature IM     110 °C
Resistance to salty wither No corrosion
Sound reduction index EN-ISO 140-3      Rw = 16 dB
Thermal   Conductivity IEEE STD 442  0,02475W/(m•K)
Thermal   Resistance   IEEE STD 442-1981
Water absorption ASTM D 2842-01  0.57
Flammability (B.S) BS 476, Part 6 & Part 7 Class 0
Flammability (EU )  EU Class B